Skip to content
Buying guide

APFC panels: what power factor correction actually saves you

Penalties, cable heating and released capacity — where the money is, how to size a bank, and where automatic correction goes wrong.

Published
19 May 2026
Reading time
7 minutes
Written by
Powertech engineering

Most industrial consumers in Telangana and Andhra Pradesh are billed on a tariff that rewards a power factor above 0.95 and penalises anything below it. An APFC panel — automatic power factor correction — is usually the fastest-paying piece of electrical equipment on a site. It is also one of the most commonly mis-specified.

Where the saving comes from

  • Penalty avoided, and often an incentive earned, on the monthly bill
  • Lower current for the same real power, so cables and switchgear run cooler
  • Released transformer capacity — correcting from 0.80 to 0.95 frees roughly 15% of your existing transformer for real load
  • Less voltage drop at the far end of long distribution runs

The third point is the one people miss. If you are considering a larger transformer because you are near capacity, correct the power factor first and measure again. It is frequently cheaper than the transformer.

Sizing the bank

The kVAr required is your real power in kW multiplied by the difference between the tangent of the present angle and the tangent of the target angle. In practice: a 500 kW load at 0.80 corrected to 0.95 needs about 500 × (0.75 − 0.33) ≈ 210 kVAr.

Split that into steps. A single 210 kVAr contactor would hunt badly at low load. Six steps of 35 kVAr, or a mixed 2-2-4-4 arrangement, gives smooth correction across the day.

Where automatic correction goes wrong

Harmonics

Capacitors present a low impedance to high frequencies. On a site with significant drive or UPS load, a plain capacitor bank can resonate with the supply and draw far more harmonic current than you expect — a failure that shows up as blown capacitor fuses within months.

The answer is detuned reactors in series with each step, usually at 7% or 14%. If your site has drives, specify a detuned panel and do not accept a plain one because it is cheaper.

Switching transients

Energising a capacitor step draws a very high inrush. Contactors intended for capacitor duty, with damping resistors, are essential; a general purpose contactor will weld its contacts.

Over-correction

Leading power factor is penalised on many tariffs just as lagging is. A controller left on a fixed setting overnight, when the plant is off and only the lighting is running, will over-correct. Set the controller to a target rather than a fixed step count.

What a well-built APFC panel contains

ComponentWhy it matters
Microprocessor PF controllerTargets a power factor rather than switching blindly
Capacitor duty contactorsRated for the inrush, with damping resistors
Detuned reactorsPrevents resonance where harmonics are present
HRC fuses per stepA failed capacitor takes out its own step, not the panel
Forced ventilationCapacitors lose life quickly above their rated temperature
Individually replaceable stepsMaintenance without shutting down correction entirely

Send us a month of half-hourly demand data and the harmonic profile if you have it. Sizing from an actual load curve beats sizing from a nameplate every time.

A reasonable expectation

On a site with a genuine penalty, an APFC panel typically pays for itself within twelve to eighteen months, and then keeps paying. What it will not do is fix a power factor problem caused by an oversized, lightly loaded motor — that is a mechanical problem wearing an electrical disguise.

Next step

Share your requirements, we’ll engineer the answer.

Send your single line diagram, rating or load list. Our engineering team responds with a technical offer.